![TEL AFA4000/E Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/tel/afa4000-e/afa4000-e_installation-and-operating-manual_1079270092.webp)
AFA4000/E
VAV Airflow Controller / p.92
Figure 60: Adjusting personnel sensor beam width
6.8.3
Adjusting the beam depth
Adjust the sensor by tilting the bottom of the sensor towards or away from the front wall of the
fume hood (Figure 61). This is to ensure that the sensors beam is at optimum angle from the
fume hood, to achieve the best field of coverage for the height of the fume hood.
The body of the Personnel Sensor can be tilted from 0
°
to 5
°
in three increments to achieve this.
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...