AFA4000/E
VAV Airflow Controller / p.126
8.2.1
ECON Configure Menu
item
Instructions
Manual / Automatic
Control output voltage can be set to Manual or Automatic
control.
Note: The controller displays Manual, Automatic, High Set
Point or Low Set Point above the output bar graph at
the top of the screen to show the current output
status.
Manual:
The output is displayed as 0
–
100%. Use the
↑
and
↓
arrows to adjust the value. Press
Mute
to select the required value. The
output will remain fixed at this value.
Note: If the Output Type is set to Valve,
the manual output is relative to the
damper position. If the Output Type
is set to Damper or Inverter, the
manual output is relative to Volume.
Automatic:
The output automatically adjusts
continuously to make the displayed face
velocity equal to the Set Point (see below).
Automatic is used for VAV control.
High Set Point
Used for the following:
•
to enter the required set point face velocity for the VAV
control
•
to enter the High Set Point face velocity in occupied
mode when Dual Set Point control is used.
Low Set Point
Used to enter the required Low Set Point velocity in
unoccupied mode when Dual Set Point control is used.
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...