AFA4000/E
VAV Airflow Controller / p.167
Setting up the dual set point:
1.
From the
Requires set up
screen, press
Mute
, or from the
Run Screen
press and hold
the
Mute
button for 5 seconds until the
Main Menu
is displayed.
2.
Select
Set Up Monitor > Configure
.
3.
Enter the password (the factory default password is 0-0-0-0) and press
Mute
to continue.
4.
Select
Input 2
>
Closed Contact
>
Pers. Sensor
.
5.
Select
Econ Config
>
High Set Point
, then use the
↑
/
↓
buttons to adjust the value to the
required High (Occupied) set point.
6.
Select
Econ Config
>
Low Set Point
, then use the
↑
/
↓
buttons to adjust the value to the
required Low (Unoccupied) set point and set the required activation delay time.
Note: The activation delay time is a delay period that activates when the fume cupboard is
unoccupied, before the controller changes to low set point operation. This allows the
user to briefly return to the fume cupboard without the controller reducing the
setpoint (0
–
300 seconds time range).
7.
Select
Cal Config Menu
>
Low Air Alarm
, then use the
↑
/
↓
buttons to adjust the value to the
required (occupied) alarm point.
8.
Select
Warning Air Alarm
, then use the
↑
/
↓
buttons to adjust the value to the required
(occupied) alarm point.
9.
Select
Reduced Low Air Alarm
, then use the
↑
/
↓
buttons to adjust the value to the required
(unoccupied) alarm point.
10.
Select
Reduced
Warning
, then use the
↑
/
↓
buttons to adjust the value to the required
(unoccupied) alarm point.
11.
Select
Done
and
Run
.
Note: The typical alarm points are:
Status
Set Point
Value
Low Air
Alarm
Warning Air
Alarm
Reduced
Low Air
Alarm
Reduced
Warning Air
Alarm
High set point
0.50 m/sec
0.40 m/sec
(80%)
0.45 m/sec
(90%)
Low set point
0.30 m/sec
0.24 m/sec
(80%)
0.27 m/sec
(80%)
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...