3.7.4
Input functions
The AFA4000/E has 3 programmable inputs that can be set to:
•
Analogue (0 - 5 Vdc)
•
Digital open operation or
•
Digital closed operation
3.7.4.1
Analogue input functions
Function
Description
Temperature
•
Any Input set to Analogue - Temperature
•
Temperature is displayed alongside airflow velocity in °C or °F (if
Show Temp
is enabled)
•
Low Temp
toggles on / off with other alarms in the status window
if temperature is less than the Low Temp Alarm point
•
Red Alarm LED Halo illuminated
•
Audible alarm sounds - can be muted by pressing the
Mute
pushbutton
•
Low Temp relay operates (when configured)
•
High Temp
toggles on / off with other alarms in the status window
if temperature is higher than the High Temp Alarm point
•
Red Alarm LED Halo illuminated
•
Audible alarm sounds - can be muted by pressing the
Mute
pushbutton
•
High Temp relay operates (if configured)
•
Temp Error
toggles on / off with other alarms in the status
window if a temperature sensor input is configured but a sensor is
not connected to the controller
•
Offset
allows the displayed temperature to be offset by ± 5°C or ±
10°F
Sash Position Sensor
•
Any Input set to Analogue
–
Sash Position
•
Used to give calculated volumetric output signal based on sash
position and airflow velocity
•
Can also be used to give Sash High Alarm
•
Sash High
toggles on / off with other alarms in the status window
if the sash height is higher than the calibrated position
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...