AFA4000/E
VAV Airflow Controller / p.148
Figure 68: Dual Output Calibration to give Reverse Output (opposite to Econ output 1 direction)
8.5.2
Volume pressure
The Volume Pressure function is used to provide a volumetric 0-10 Vdc output relative to the
fume cupboard extract volume. The controller power supply is fitted with a pressure cell PCB
and connects to a bell mouth venturi type restrictor in the duct. The restrictor can be provided
as a separate item or built into the Econ damper section.
3
rd
party restrictor devices or orifice plates can also be used with the pressure cell PCB.
The volumetric output is provided as an analogue 0-10 Vdc signal on Econ Output 2 and is also
available on the RS485 comms output.
Max Output
Min Output
First Bleed Cal
Point e.g. 100%
Second Bleed Cal
Point e.g. 0%
First Bleed Cal
Sash Position
e.g. 500mm
Second Bleed Cal
Sash Position
e.g. 100mm
DUAL OUTPUT
ECON OUTPUT
0V
10V
10V
DUAL OUTPUT CALIBRATION
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...