AFA4000/E
VAV Airflow Controller / p.23
Alarm
Description
•
Low air relay operates (if configured)
Reset: when airflow rises 0.02 m/sec above Low air level for
longer than the low air to warning air delay time, the Low air
alarm resets automatically
High airflow
If configured:
•
Airflow reading above high level (for example > 1.50 m/sec)
•
Red Alarm LED Halo illuminated
•
High Air
displayed in the status window or main window if
Show Airflow is set to OFF.
•
Audible alarm sounds - can be muted by pressing the
Mute
pushbutton
•
High air relay operates (when configured)
3.7.2
Audible alarm mute
When the audible alarm is muted via the
Mute
button, an icon (
) displays.
The audible alarm can be permanently disabled by selecting
Not Enabled
in the
Cal Config menu
(
Setup Monitor > Configure > Cal Config Menu > Audible Alarm
).
3.7.3
Pushbutton functions
The AFA4000/E has 3 programmable pushbuttons. The pushbutton icon is displayed on the
screen, above the relevant pushbutton. The pushbuttons are identified as Pushbutton I,
Pushbutton II and Pushbutton III.
Each Pushbutton has a Power Up Memory function. The Power Up Memory function sets the
pushbutton back to its last status, following a power fail cycle. For example, when the Fan is On
during a power failure, the AFA4000/E powers up with the Fan pushbutton set to On.
Each pushbutton has a PIN option selectable as PIN required for On,
PIN required for Off or PIN
required for both On and Off. When a PIN option is enabled, a New PIN parameter appears,
allowing you to set a 4-digit PIN number.
When a PIN is enabled and the pushbutton is pressed, a Password screen displays. If the correct
PIN is entered the pushbutton action will be completed; if an incorrect PIN is entered the
pushbutton action will remain in its present condition.
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...