AFA4000/E
VAV Airflow Controller / p.45
4.3.5
Sash Low switch
When a Tiptronic control is not in use, a Sash Low switch is used to signal to the Auto Sash
Control Unit that the fume hood sash is closed.
The switch can be either a mechanical roller lever type micro-switch or an inductive proximity
switch.
Roller Lever Micro-Switch
Inductive Proximity Switch
Figure 10: Typical Sash Low switches
4.3.6
Sash Position sensor
The Sash Position Sensor comprises of a flexible cable, a spring-loaded spool and a
potentiometer. It is used, in conjunction with the Tiptronic control option, to detect and
measure vertical sash movement and the position of the fume hood sash.
During the initial on-screen calibration set up the sash controller detects the sensor direction of
travel and then provides position information of the sash to the Auto Sash Control Unit, to
enable calibration of the sash open / closed positions.
Sash Position Sensor
Sensor Cable
Sensor Potentiometer
Figure 11: Sash Position Sensor
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...