AFA4000/E
VAV Airflow Controller / p.25
When Pushbutton I is set to Fan On/Off, the following additional functions appear in the
Pushbutton I configuration menu:
Function
Description
Interlock
•
Not active
•
Off enable PB2. Pushbutton II is switched and held OFF if
pushbutton I is ON.
•
On enable PB2. Pushbutton II is switched and held OFF if
pushbutton I is OFF.
•
On Run Up enable PB2. Pushbutton II is enabled when
Pushbutton I run up timer has elapsed.
Run Up Timer
•
Not enabled / enabled. When enabled, select the Run Up
Timer relay and set the Run Up Time.
When the fan is set to ON, the Run Up Timer activates after
the Run Un Time. This function is used when 2 output relays
are required for Pushbutton I.
Run Down Timer
•
Enabled / not enabled. When enabled, select the Run Down
Time.
When the fan is set to OFF, the fan remains on for the set
time, and a down arrow next to the pushbutton icon appears
to indicate that the Run Down Timer is active.
3.7.3.2
Pushbutton II
Function
Description
Lights On / Off
•
Pushbutton II set to
Lights On / Off
•
Lights On / Off Relay operates
UV Lights On / Off
•
Pushbutton II set to
UV Lights On / Off
•
UV Lights On / Off Relay operates
Services On / Off
For Australian Standards Operation only. This requires a special
software version.
The following parameters should be set:
•
Pushbutton I icon set to Fan On/Off, Relay Output 1
•
Pushbutton I interlock = On Run Up Pb2
•
Pushbutton I interlock Run Up Timer = set to the required pre-
purge time
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...