AFA4000/E
VAV Airflow Controller / p.128
item
Instructions
Output Type (cont.)
Figure 66: Typical linearised butterfly damper curve to face
velocity (Damper Output)
Note: Performance is dependent on damper and fume
cupboard leakage.
MIN Output
Used when Pushbutton III is set to Min / Run / Max.
MIN Output
sets the damper or inverter to a minimum
extract volume when the fume cupboard is not in use and
the MIN function is selected.
Output range: 0
–
100%
MAX Output
Used when Pushbutton III is set to Min / Run / Max.
MAX Output
sets the damper or inverter to a maximum
extract volume in an emergency when the MAX function is
selected.
Output range: 0
–
100%
Low Limit
Used to set up the minimum extract rate from the fume
cupboard in automatic VAV operation. As the sash is
lowered, the damper progressively closes, or extract fan
slows down, to reduce the extract volume and maintain the
set point face velocity. The Low Limit sets a minimum
damper position to prevent the volume reducing too far.
As the sash is lowered, the displayed face velocity will be at
the set point value until the damper reaches the Low Limit.
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...