AFA4000/E
VAV Airflow Controller / p.130
item
Instructions
Prop Band (cont.)
The ideal setting is to select a value that is as small as
possible which gives stable control of the damper or inverter
without ‘hunting’. (Refer to section
0 for a practical
explanation of how to set this value on a fume cupboard).
Example Prop Band gain settings:
P Band
%
Set Point
m/sec
Integral
Secs
Output = 0% @
Output = 100% @
50
0.50
0
0 m/sec
1.00 m/sec
30
0.50
0
0.20 m/sec
0.80 m/sec
10
0.50
0
0.40 m/sec
0.60 msec
The Prop Band gain is 0
–
100% of full scale (1.00 m/sec), so
if a Prop Band of 50% = 0.5 m/sec, the output will be at zero
when the airflow is 0.5 m/sec below the set point and be at
100% when the airflow is 0.5 m/sec above the set point.
Integral Time
The Integral Time is the correction action of the control
system. If only proportional control (prop band) is used, any
error is between the actual measured face velocity and the
set point face velocity. The Integral action takes this error
and adjusts the control output in a series of small steps to
bring the measured value to the same as the set point value.
The time taken to correct the measured value depends on
how many times the controller makes the small adjustments
over a period of time.
The Integral Time action is shown on the menu in Seconds.
Increasing the value will give a faster correction time.
If the value is set too low, it will take a long time for the
measured value to reach the set point. If it is set too high,
the measured value will correct very quickly but may
‘overshoot’ in each direction and cause ‘hunting’.
Содержание AFA4000/E
Страница 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Страница 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Страница 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Страница 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Страница 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Страница 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Страница 71: ...AFA4000 E VAV Airflow Controller p 71 Figure 34 Side views of a rack and pinion drive typical installation...
Страница 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Страница 158: ...AFA4000 E VAV Airflow Controller p 158...
Страница 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...