4-18
Group 07: Start/Stop Parameters
No.
Description
Range
Factory
Setting
Unit
Note
07-00
Momentary Power Loss and
Restart
0: Momentary Power Loss and Restart Disable
1: Momentary Power Loss and Restart Enable
0
-
07-01
Auto Restart Delay Time
0.0~800.0
0.0
Sec
07-02
Number of Auto Restart
Attempts
0~10
0
-
07-03
Reset Mode Setting
0: Enable Reset Only when Run Command is Off
1: Enable Reset when Run Command is On or Off
0
-
07-04
Direct Running on Power
Up
0: Enable Direct run on power up
1: Disable Direct run on power up
1
-
07-05
Delay-ON Timer
1.0~300.0
1.0
Sec
07-06
DC Injection Brake Start
Frequency
0.10 ~ 10.00
1.5
Hz
07-07
DC Injection Brake Level
(Current Mode)
0.0 ~ 150.0
50.0
%
07-08
DC Injection Brake Time
0.0 ~ 25.5
0.5
Sec
07-09
Stopping Method
0: Deceleration to stop
1: Coast to stop
0
-
07-10
Starting Methods
0: Normal Start 1: Speed Search
0
-
07-11
Starting method for auto
restart after fault
0: Speed Search 1: Normal start
0
-
07-12
Power Loss Ride Through
Time
0.0 ~ 2.0
0.5
Sec
07-13
Main Circuit Low Voltage
Detection Level
150.0~210.0 300.0~420.0
190.0/38
0.0
Vac
07-14
Kinetic Energy Back-up
Deceleration Time
0.0~25.0: KEB Deceleration Time
0.0
Sec
07-15
DC Injection Brake Mode
0 : Current Mode 1 : Voltage Mode
1
-
*6
07-16
DC Injection Brake Level
(Voltage Mode)
0.0~10.0
4.0
%
*6