4-9
G r o u p 00: Basic parameters
No.
Description
Range
Factory
Setting
Unit
Note
00-00
Control Mode Selection
0:V/F Mode
0
-
1:Vector Mode
00-01
Reserved
00-02
Main Run Command
Source Selection
0:Keypad
0
-
1:External Run/Stop Control
2:Communication
3:PLC
00-03
Alternative Run Command
Source Selection
0:Keypad
0
-
1:External Run/Stop Control
2:Communication
00-04
Operation Modes for
External Terminals
0:Forward/Stop-Reverse/Stop
0
-
1:Run/Stop- Reverse/Forward
2: 3 Wire Control Mode-Run/Stop
00-05
Main Frequency Command
Source Selection
0:UP/DOWM of Keypad
0
-
1:Potentiometer on Keypad
2:External AI1 Analog Signal Input
3:External AI2 Analog Signal Input
4:External Up/Down Frequency Control
5:Communication Setting Frequency
6:PID Ouput Frequency
7:Pulse Input
*6
00-06
Alternative Frequency
Command Source Selection
0:UP/DOWM of Keypad
4
-
1:Potentiometer on Keypad
2:External AI1 Analog Signal Input
3:External AI2 Analog Signal Input
4:External Up/Down Frequency Control
5:Communication Setting Frequency
6:PID Ouput Frequency
7:Pulse Input
*6
00-07
Main and Alternative
Frequency Command Modes
0:Main or Alternative Frequency
1:Main Fr Alternative
Frequency
0
-
00-08
Communication
Frequency Command
0.00~650.00
60.00
Hz
*4
00-09
Frequency Command
Save on Power Down
0: Disable
0
-
1: Enable
00-10
Initial Frequency
Selection (keypad mode)
0:by Current Frequency Command
0
-
1:by 0 Frequency Command
2:by 00-11
00-11
Initial Frequency Setpoint
0.00~650.00
50.00/60.00
Hz
00-12
Frequency Upper Limit
0.01~650.00
50.00/60.00
Hz
00-13
Frequency Lower Limit
0.00~649.99
0.00
Hz
00-14
Acceleration Time 1
0.1~3600.0
10.0
Sec
*1
00-15
Deceleration Time 1
0.1~3600.0
10.0
Sec
*1
00-16
Acceleration Time 2
0.1~3600.0
10.0
Sec
*1
00-17
Deceleration Time 2
0.1~3600.0
10.0
Sec
*1
00-18
Jog Frequency
0.00~650.00
2.00
Hz
*1*7
00-19
Jog Acceleration Time
0.1~3600.0
0.5
Sec
*1*7
00-20
Jog Deceleration Time
0.1~3600.0
0.5
Sec
*1*7