4-11
Group 03: External Digital Inputs and Relay Output Functions
No.
Description
Range
Factory
Setting
Unit
Note
03-00
Multifunction Input Term. S1
0:Forward/Stop Command
0
-
03-01
Multifunction Input Term. S2
1:Reverse/Stop Command
1
-
03-02
Multifunction Input Term. S3
2:Speed Selection 1
2
-
03-03
Multifunction Input Term. S4
3:Speed Selection 2
3
-
03-04
Multifunction Input Term. S5
4:Speed Selection 3
4
-
03-05
Multifunction Input Term. S6
5:Speed Selection 4
17
6:Jog Forward Command
7:Jog Reverse Command
8:Up Command
9:Down Command
10:Acc/Dec 2
11:Acc/Dec Disabled
12:Main/Alternative run source
select
13:Main/ Alternative Frequency
Command select
14:Rapid Stop ( Decel to stop )
15:Base Block
16:Disabl PID Function
17:Fault Reset
18:Auto Run Mode Enable
19:Speed Search
20:Energy Saving (only V/F)
21:Reset PID integral value to Zero
22:Counter Input
23:Counter reset
24:PLC Input
25:Pulse Input-Width Measure (S3)
*6
26:Pulse Input-Frequency Measure (S3)
*6
27:Enable KEB Function
28:Fire mode function
*5
03-06
Up/Down frequency step
0.00~5.00
0.00
Hz
03-07
Up/Down Keep Frequency Status after
Stop Command
0:When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down function is disabled
0
-
1:When Up/Down is used, the preset
frequency is reset to 0 Hz as the inverter
stops.
2:When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down is available.
03-08
S1
~
S6 scan confirmation
1~200 Number of Scan cycles
10
2ms
03-09
S1~ S5 switch type select
xxxx0:S1 NO xxxx1:S1 NC
00000
-
xxx0x:S2 NO xxx1x:S2 NC
xx0xx:S3 NO xx1xx:S3 NC
x0xxx:S4 NO x1xxx:S4 NC
0xxxx:S5 NO 1xxxx:S5 NC
03-10
S6 switch type select
xxxx0:S6 NO xxxx1:S6 NC
00000
-
03-11
Output Relay RY1
0:Run
0
-