4-10
G r o u p 01: V/F Control Parameters
No.
Description
Range
Factory
Setting
Unit
Note
01-00
Volts/Hz Patterns
0~18
0/9
-
01-01
V/F Max voltage
200V:170.0~264.0
400V:323.0~528.0
220.0/440.0
Vac
01-02
Max Frequency
0.20 ~ 650.00
50.00/60.00
Hz
01-03
Max Frequency Voltage Ratio
0.0 ~ 100.0
100.0
%
01-04
Mid Frequency 2
0.10 ~ 650.00
25.00/30.00
Hz
01-05
Mid Frequency Voltage Ratio 2
0.0 ~ 100.0
50.0
%
01-06
Mid Frequency 1
0.10 ~ 650.00
10.00/12.00
Hz
01-07
Mid Frequency Voltage Ratio 1
0.0 ~ 100.0
20.0
%
01-08
Min Frequency
0.10 ~ 650.00
0.50/0.60
Hz
01-09
Min Frequency Voltage Ratio
0.0 ~ 100.0
1.0
%
01-10
Volts/Hz Curve Modification
(Torque Boost)
0 ~ 10.0
0.0
%
*1
01-11
V/F start Frequency
0.00~10.00
0.00
Hz
01-12
Slip compensation gain
0.05~10.00
0.10
S
01-13
V/F Mode Select
0 : Mode 0 1 : Mode 1
by models
-
G r o u p 02: IM Motor parameters
No.
Description
Range
Factory
Setting
Unit
Note
02-00
Motor No Load Current
0~[(Patameter 02-01)-0.1]
-
Amps(AC)
*3
02-01
Motor Rated Current (OL1)
0.2~100
-
A
*3
02-02
Motor rated Slip Compensation
0.0 ~ 200.0
0.0
%
*1
02-03
Motor rated speed
0~39000
-
Rpm
*3
02-04
Motor rated voltage
200V: 170.0~264.0
400V: 323.0~528.0
220.0/440.0
V
02-05
Motor rated power
0.1~37.0
-
KW
02-06
Motor rated frequency
0~650.0
50.0/60.0
Hz
02-07
Motor pole number
2 ~16
4
-
02-08
~
02-13
Reserved
02-14
Auto Tune
0: Disable
0
1: Start Auto tune function.
02-15
Stator resistance gain
----
*3*4
02-16
Rotor resistance gain
----
*3*4