11-19
FWD
REV
Preset Freq. Reached
Setting (03-13)
Preset Freq. Reached Detection Range (03-14)
When Output Freq. = Preset Freq. Reached Setting (03-13)
–
Preset Freq.
Reached Detection Range (03-14), Relay Output will be ON
Output Freq.
ON
ON
Relay Output
Hz
Time
0
RUN
RUN
Run Command
(03-13)
–
(03-14)
Preset Freq. Reached
Detection Range, (03-14)
(03-13) - (03-14)
Preset Freq. Reached
Setting (03-13)
Example:
Sets 03-13=30 and 03-14=5, Relay is ON when output frequency is >=25Hz and <= 30Hz.
03-11=
【
3
】
: Set Frequency reached
Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequency
detection level (03-13).
FWD
REV
Setting Freq. 2
Setting Freq. 1
Setting Freq. 1
Setting Freq. 2
2*Preset Freq. Reached Detection
Range (03-14)
Relay Output
ON
ON
ON
RUN
RUN
RUN
RUN Command
FWD
Hz
Time
0
When, Freq. Detection Range Lower Limit
<Setting Freq.<
Freq. Detection Range Upper Limit
and Detection Range Lower Limit
<Output Freq.<
Freq. Detection Range Upper Limit
Relay output is ON
(
Allowable tolerance ±0.01
)
(
03-13
)
(03-13)+(03-14)
(03-13)-(03-14)
(03-13)
(03-13)-(03-14)
(03-13)+(03-14)
2*Preset Freq. Reached Detection
Range (03-14)
Freq. Detection Range Upper Limit
Freq. Detection Range Lower Limit
03-11=
【
4
】
:
Output Frequency Detection 1
Output is active when the output frequency rises above the frequency detection level (03-13) and deactivates when
the output frequency falls below frequency detection level (03-13).