11-13
Example:
00-12 (Frequency upper limit) =60Hz
03-00= 0 (Terminal S1 FWD/STOP)
00-14 (accelerating time 1) = 10 sec
00-16 (accelerating time 2) =5 sec
60Hz
0
10s
(accel time 1)
Hz
T
5s
(accel time 2)
S1 Off
S1 On
03-00~03-05=
【
11
】
Disable Acc/Dec function
When activated suspends the acceleration / deceleration operation and maintains the output frequency at current
level.
Accel/Decel & Enable/Disable timing diagram using terminal S1 and parameter 03-00 = 11.
RUN
Command
S1
RUN
STOP
ON
OFF
ON
OFF
T
Hz
03-00~03-05=
【
12
】
Main / Alternative Run Source Select
When active, the run command source is set by parameter 00-03(Alternative Run source). When Input is off run
command source is set by parameter 00-02 (Main run source).