11-3
00-05
Main Frequency Command Source Selection
00-06
Alternative Frequency Source Selection
Range
【
0
】
:Up/Down on Keypad
【
1
】
:Potentiometer on Keypad
【
2
】
:External AI1 Analog Signal Input
【
3
】
:External AI2 Analog Signal Input
【
4
】
:External Up/Down Frequency Control
【
5
】
:Communication Setting Frequency
【
6
】
:PID Output Frequency
【
7
】
:Pulse Input
00-05/00-06= 0:
Keypad
Use the keypad to enter the frequency reference or by setting parameter 05-01 (frequency reference 1). Note that
once the frequency command is switched to alternative frequency reference and 00-06 is set to 0, the frequency
can be adjusted using parameter 05-01.
00-05/00-06= 1:
Potentiometer on Keypad
Use the keypad potentiometer to set frequency reference
00-05/00-06= 2, 3:
External Analog Input AI1 / External Analog Input AI2
Set any of the multi-function terminals (03-00~03-05) to 13, to switch between main and alternate frequency.
Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in Figure 4.3.4).
Refer to parameter 04-00 to select the signal type.
04-00
Analog Input Signal Type Select
(AI1/AI2)
AI1 AI2
(0): 0~10V (0~20mA) 0~10V (0~20mA)
(1): 0~10V (0~20mA) 2~10V (4~20mA) Factory Default
(2): 2~10V (4~20mA) 0~10V (0~20mA)
(3): 2~10V (4~20mA) 2~10V (4~20mA)
JP2/JP3
External signal type
selection
0~20mA / 4~20mA
Analog signal
0~10VDC / 2~10VDC
Analog signal