below the setting of parameter 08-0301 after which acceleration resumes back to the target frequency.
08-04
Over Voltage Prevention Level During Run Mode
Range
【
350.0VDC~390.0VDC
】
(230V class)
【
700.0VDC~780.0VDC
】
(460V class)
Over voltage prevention level can be set by parameter 08-04 if needed.
When the DC bus voltage rises above level set in 08-04 an over voltage fault will occur.
08-05
Electronic Motor Overload Protection Operation Mode (OL1)
Range
【
0
】
: Disable
【
1
】
: Enable
The electronic motor overload protection function estimates the motor overload level based on the output current,
output frequency, motor characteristics and time. The motor overload trip time depends on the motor rated
current when the output current is greater than motor FLA.
12-00
Display Mode
Range
0 0 0 0 0
MSD LSD
00000~88888 Each digit can be set from 0 to 8 as listed below.
【
0
】
:Disable display(frequency& parameters)
【
1
】
:output Current
【
2
】
:output Voltage
【
3
】
:DC voltage
【
4
】
:Temperature
【
5
】
:PID feedback
【
6
】
:AI1
【
7
】
:AI2
【
8
】
:Count Status
Note:
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the
display sequence see chapter 4.1.3.
12-01
PID Feedback Display format
Range
【
0
】
:Displayed in Integer (xxx)
【
1
】
:One Decimal Place (xx.x)
【
2
】
:Two Decimal Places (x.xx)
12-02
PID Feedback Display Unit Setting
Range
【
0
】
:xxx--
【
1
】
:xxxpb(pressure)
【
2
】
:xxxfl(flow)
12-03
Custom Units (Line Speed) Display Mode
Range
【
0~65535
】
Rpm
Set motor rated RPM for the inverter to display the actual motor speed based on the output frequency.
Motor synchronous speed = 120 x Rated frequency ÷ Number of poles.