11-10
2-Wire control method
Example:
FWD/STOP and REV/STOP from two inputs (S1 & S2)
Set 00-04=
【
0
】
; S1:03-00=
【
0
】
(FWD/STOP); S2:03-01=
【
1
】
(REV/STOP);
E510
S1
S2
COM
(FWD/STOP)
(REV/STOP)
S1
ON
OFF
FWD
REV
ON
OFF
S2
Hz
T
Note:
If both forward and reverse commands are active the inverter treats this as a STOP command.
3-Wire control method
Example:
Two separate push buttons for RUN & STOP and two position selector switch for FWD/REV
Set 00-04 =
【
2
】
, (3 wire control mode), to set terminals S1, S2 and S3 for 3-Wire control
When 3-Wire control mode is selected the setting for parameters 03-00, 03-01 and 03-02 are not active.
E510
S1(RUN)
S2(STOP)
S3(FWD/REV)
COM