11-14
03-00~03-05=
【
13
】
Main/ Alternative Frequency Source Select
When active the Alternative Frequency Source parameter 00-06 is used, otherwise Main Frequency Source is
used parameter 00-05.
03-00~03-05=
【
14
】
Rapid Stop (controlled deceleration stop)
When active inverter decelerates to stop using deceleration time 2.
03-00~03-05=
【
15
】
Base Block (Coast to stop)
When active the inverter output is turned off.
03-00~03-05=
【
16
】
Disable PID Function
When active PID function is disabled.
03-00~03-05=
【
17
】
Reset
When active inverter resets active fault (same function as the Reset button on the keypad).
03-00~03-05=
【
18
】
Auto _ Run Mode
When active the programmable auto- sequencer function is enabled, Refer to description of parameter group 6.
03-00~03-05=
【
19
】
Speed Search Stop
When active the inverter performs a speed-search by detecting the current speed of the motor and accelerating
from there to the target speed.
03-00~03-05=
【
20
】
Energy-saving operation
When active the inverter output voltage is gradually decreased to match the required torque demand and as a
result saves energy. Only for variable torque applications such as fans and pumps that require less torque when
operation speed is reached. When input is turned off the output voltage gradually increases again back to the
original output voltage.
Note:
Acceleration and deceleration times in energy saving operation is identical to that of speed search
operation.
03-00~03-05=
【
21
】
Reset PID Integral value to Zero
When active resets the PID integral value zero.
03-00~03-05=
【
22
】
Counter Input
Input used as counter input, set related parameters 03-21 ~03-22.
Count status can be viewed by setting parameter 12-00 to 8
Count Input
Multi-function input
2ms
c0000 c0001 c0002 c0003 c0004 c0005 c0006 c0007
Count display set
by 12-00 = 8