11-25
04-11
Analog Output (AO) Function Selection.
Range
【
0
】
:Output Frequency
【
1
】
:Frequency Command
【
2
】
:Output Voltage
【
3
】
:DC Bus Voltage
【
4
】
:Output Current
Example:
Set 04-11 as required according to the table below.
0
10V
Xmax
A
Xmax( 04-11)
Xmax/2
5 V
04-12
AO Gain
Range
【
0 ~ 1000
】
%
04-13
AO Bias
Range
【
0 ~ 100
】
%
04-14
AO Bias Selection
Range
【
0
】
: positive
【
1
】
: Negative
04-15
AO Slope
Range
【
0
】
: positive
【
1
】
: Negative
04-16
F-Gain
Range
【
0
】
: Invalid
【
1
】
: Effective
Set Analog output function (04-11).
Output level is 0-10Vdc.
Output voltage level can be scaled and adjusted with parameters 04-12 to 04-15 if needed.
The analog output scaling is the same as examples shown previously for Analog Voltage Input (AI1) parameters
4-02 to 4-05.
Note:
The max output voltage is 10Vdc based on the inverter hardware. Use external devices that require a maximum
of 10Vdc signal.
07-00
Momentary power loss and restart
Range
【
0
】
:Momentary Power Loss and Restart Disable
【
1
】
:Momentary Power Loss and Restart Enable
Inverter output will be turned off during a sudden drop in input voltage below the under voltage level.
04-11
A
Xmax
【
0
】
Output frequency
upper frequency limit
【
1
】
Frequency Setting
upper frequency limit
【
2
】
Output voltage
Motor Rated Voltage
【
3
】
DC Bus Voltage
230V: 0~400VDC
460V: 0~800VDC
【
4
】
Output current
rated current of
inverter