Group 08: Protection Parameters
No.
Description
Range
Factory
Setting
Unit
Note
08-14
Over torque protection
action
0: Stop Output After Over Torque Detection (Free Run to
Stop)
0
-
1: Continue Running After Over Torque Detection (Display
only OL3)
08-15
Over Torque Detection
Level
30~300
160
-
08-16
Over Torque Detection
Time
0.0~25.0
0.1
-
08-17
Fire Mode
0: Disable
0
-
*5
1: Enable
08-18
Ground Fault Detection
0: Disable
0
*7
1: Enable
Notes: F
ire mode function
1.
Before the firmware rev. 1.1, the fire mode is enabled when parameter 08-17 = 1
2.
After the firmware 1.1, the firemode is enabled when any of parameters 03-00~03-05 is set to a value of 28
3.
The keypad display will indicate FIrE
4. In fire mode the inverter will run at full speed
5. Parameter 08-18 is only displayed in the frame 3, 4 models
Group 09: Communication Parameters
No.
Description
Range
Factory
Setting
Unit
Note
09-00
Assigned Communication
Station Number
1 ~ 32
1
-
*2*3
09-01
RTU/ASCII Code Selection
0:RTU Code
1:ASCII Code
0
-
*2*3
09-02
Baud Rate Setting (bps)
0:4800
1:9600
2:19200
3:38400
2
bps
*2*3
09-03
Stop Bit Selection
0:1 Stop Bit
1:2 Stop Bits
0
-
*2*3
09-04
Parity Selection
0:Without Parity
1:With Even Parity
2:With Odd Parity
0
-
*2*3
09-05
Data Format Selection
0: 8-Bits Data
1: 7-Bits Data
0
-
*2*3
09-06
Communication Time-Out
Detection Time
0.0 ~ 25.5
0.0
Sec
09-07
Communication Time Out
Operation Selection
0:Deceleration to Stop
(00-15: Deceleration Time 1)
1:Coast to Stop
2:Deceleration to Stop
(00-17: Deceleration Time 2)
3:Continue Operating
0
-
09-08
Comm. Fault Tolerance Count.
1 ~ 20
3
09-09
Wait Time of Inverter Transmission
5 ~ 65
5
ms