9.3 Engineering Units
PID Feedback Display Scaling
The PID feedback signal can be scaled to represent actual engineering units. Use parameter 10-21 to set the
feedback signal gain for the feedback signal range maximum and parameter 10-22 to the feedback signal
minimum.
Example:
Feedback signal is a pressure transducer (0-10V/0-20mA) with a range of 0
– 200 PSI
0V/0mA = 0 PSI, 10V/20mA = 200 PSI.
Set parameter 10-21 to 200 maximum of transducer range (100%).
Set parameter 10-22 to 0 minimum of transducer range (0%).
Feedback
10V
( 20mA )
0V
( 0mA )
10-21
10-22
Display unit