8-4
8.4
Rapid Stop
Deceleration time 2 is used in combination with multi-function digital input function #14 (Rapid stop). When rapid
stop input is activated the inverter will decelerate to a stop using the Deceleration time 2 (00-17) and display the
[E.S.] condition on the keypad.
Note:
To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Emergency Stop Switch set for input terminal S5 (03-04 = 14).
24V
AI1
AGND
R1A
R1B
10V
AO
R2B
R2B
COM
S1
S3
S5
SF
AI2
R1C
S2
S4
S6
SG
Emergency
Stop Switch
Emergency Stop
Common
Control Terminals /
User Terminals
00-17
Deceleration Time 2
Range
0.1~3600.0 Sec