11-12
03-0X =
【
06
】
:
Forward jog run command, uses jog frequency parameter 00-18.
Note:
Jog command has a higher priority than other frequency reference commands.
Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms.
03-0X =
【
07
】
:
Reverse jog run command, uses jog frequency parameter 00-18.
Note:
Jog command has a higher priority than other frequency reference commands.
Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms.
Note:
If Forward and Reverse Jog are active at the same time the inverter enters stop mode.
03-0X =
【
08
】
:
UP frequency command; set parameter 00-05 Frequency command to 4 to activate. When ON
frequency reference increased by value set in parameter 03-06. If the input is kept on continuously, the frequency
command increases accordingly until the upper frequency limit is reached.
03-0X =
【
09
】
:
Down frequency command; set parameter 00-05 Frequency command to 4 to activate. When ON
frequency reference decreased by value set in parameter 03-06. If the input is kept on continuously, the
frequency command decreases accordingly and in relation to settings for parameter 03-06 and 3-07 until zero
speed is reached.
UP Command
(Terminal S5)
1
0
0
1
Down Command
(Terminal S6)
0
1
0
1
Operation
Accel
(UP)
Decel
(DWN)
Hold
Hold
03-00~03-05=
【
10
】
2nd Acc/Dec time
When active the acceleration and deceleration time will be set according to value set in parameter 00-16
(acceleration time 2) and 00-17 (deceleration time 2).
When not-active the acceleration and deceleration time will be set according to value set in parameter
00-14(acceleration time 1) and 00-15 (deceleration time 1).
S1 Forward Run / Stop (03-00 = 0)
COM
S5 Up Command (03-04=8)
S6 Down Command (03-04=9)