A-4
Main Circuit Terminal Wiring
UL approval requires crimp terminals when wiring the inverter
’s main circuit terminals. Use crimping tools as
specified by the crimp terminal manufacturer. TECO recommends crimp terminals made by NICHIFU for the
insulation cap.
The table below matches inverter models with crimp terminals and insulation caps. Orders can be placed with a
TECO representative or directly with the TECO sales department.
Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
Terminal
Crimp
Terminal
Tool
Insulation Cap
mm2 , (AWG)
E510
R/L1 / S/L2 /
T/L3
U/T1 / V/T2 /
W/T3
Screws
Model No.
Machine No.
Model No.
201
2.1 (14)
M3.5
R2-3.5
Nichifu NH 1 / 9
TIC 2
202
3.3(12)
M4
R3.5-4
Nichifu NH 1 / 9
TIC 3.5
202-H3
2.1 (14)
M3.5
R2-3.5
Nichifu NH 1 / 9
TIC 2
205
5.3(10)
M4
R5.5-4
Nichifu NH 1 / 9
TIC 5.5
210
8.4(8)
M5
R8-5
Nichifu NH 1 / 9
TIC 8
220
21.2(4)
M5
R22-5
Nichifu NOP 150H
TIC 22
402
2.1 (14)
M3.5
R2.3.5
Nichifu NH 1 / 9
TIC 2
405
2.1 (14)
M4
R2.3.5
Nichifu NH 1 / 9
TIC 2
415
8.4(8)
M5
R8-5
Nichifu NH 1 / 9
TIC 8
425
8.4(8)
M5
R8-5
Nichifu NH 1 / 9
TIC 8
Type 1
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.