Instruction Manual
ITEM TE700
TECNA
S.p.A.
106/128
The max number of welds to be carried out is adjusted by adhering to the same procedure
described for the stepper function. Since there is one stepper module for each spots counter,
the operator may define for each available tool or welding head after how many spots the
control unit must prevent the selected tool from carrying out any more welds.
For example, if the operator wants the control unit to carry out 2840 welds with tool 1 and
then stop, he/she must set the following parameters in the
STEPPER MENU
:
STEPPER MENU T1
>TOOLS N° 1
STEPPER WELD ON L1
STEPPER TIME OFF
PARAMETER
PARAMETER DESCRIPTION
VALUE
TOOLS N°
Number of the tool in which a limit is to be set
1
STEPPER WELD
Stepper function activation with increase of 0
ON L1
STEPPER TIME
OFF
STEPPER THICK.
OFF
N.TOTAL STEPS
1
SPOTS 1
Number of spots after which the unit must stop
02840
INCREMENT 1-L1
00%
INCREMENT 1-L2
00%
Further information about the parameters is supplied in the
STEPPER
function paragraph.
When the counter reaches the set welds number, the control unit displays the following
message:
STOP [167]
N SPOT MAX
WARNING ON TOOLS T1
PUSH [///] TO RESET
and will not permit carrying out any other welds until the counter is cleared.
If the STEPPER WELD parameter is set to OFF, the stop function is disabled.