Appendix B: Calibration, Maintenance, and Care
BlowerDoor Standard
January 2022
81
Reset DG-1000
A recovery disk (micro-SD card) is available from BlowerDoor GmbH. It should be used only if you need
to reset the DG-1000 to the factory settings.
If a situation arises where the recovery disk may need to
be used, consult with BlowerDoor GmbH technical support.
B.2
BlowerDoor Fan
Calibration parameters for Models 4 and 4.1
Fan configuration
Calibration parameters
Air flow readings
C
n
Open fan
flow (m³/h) =
745.4
∙
(fan pressure in Pa)
0.4848
Ring A installed
flow (m³/h) =
273.2
∙
(fan pressure in Pa)
0.4952
Ring B installed
flow (m³/h) =
81.69
∙
(fan pressure in Pa)
0.4968
Ring C installed
flow (m³/h) =
19.30
∙
(fan pressure in Pa)
0.5157
Ring D installed
flow (m³/h) =
12.31
∙
(fan pressure in Pa)
0.5032
Ring E installed
flow (m³/h) =
4.761
∙
(fan pressure in Pa)
0.5166
Note:
All air flow measurements shown on the DG-1000 are adjusted to an air density standard of
1.204 kg/m³. This corresponds to an air density under ambient conditions of 20° C and 101325 Pa.
The adjustment is based on the CGSB regulation CAN/CG-SB-149.10-M86. This measurement does not
include the actual airflow through the fan.