7 Leakage Detection Using the DG-
Cruise Control (without laptop)
66
January 2022
BlowerDoor Standard
Fig. 7.3
Selecting the measuring mode
When the device turns on, it is set to
Pressure (Pa)
(channel A, see on the top in the left cell)
.
For
channel B, the last selected setting is set (see on the
top in the right cell).
•
To change, touch the currently displayed
measurement mode at the top of the right cell.
Fig. 7.4
•
Select mode
Q@50 (m³/h)
on Channel B.
“Q”
signifies flow.
In this mode, Channel A measures the building
pressure differential. Channel B displays the
calculated airflow at 50 Pa. The magnitude of this
airflow depends on the size of the flow ring
installed and the speed of the fan.
•
Use the arrow
to return to gauge screen.
Fig. 7.5
Choosing the flow ring and the BlowerDoor model
•
Install the desired flow ring on the fan. It is
recommended to begin with ring C (to avoid
excessive pressure differentials).
•
On the DG-1000, the fan model and the flow ring
configuration must be set accordingly.
•
To change, touch the currently displayed fan
model or ring at the bottom of the right cell.