~31~
Try to far away from inverter and its input and output wires.
If the signal cable must cross power cable, keep orthogonality between them.
(2) Connect output line into ground metal tube. The interval distance between
output line and signal line is more than 30cm.
(3) On the output side of the inverter, install special radio noise filter and linear
noise filter
(
ferrite common-mode retardation coil
)
to restrain radiation noise
of power line.
(4) Avoid parallel wiring or bundle wiring between signal line and power line
,
make easy-effected equipments aways from the inverter, make easy-effected
signal away from input and output lines of the inverter.
It is better that shield signal line and power line, and respectively put into metal
tubes. The interval distance between metal tubes is more than 20mm.
(5) Shield with steel vessel. Connection line between inverter and the motor should
be as short as possible.
3.7 Wiring inspection
After wiring is completed, please inspect the wiring.
Connection is right, or not;
Screws and wire terminals are left in the equipment, or not;
Screws are loose, or not;
The bare wire of terminal parts is short-circuiting to other terminals, or not.
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...