User Manual of SY5000 series AC Drive MODBUS communication protocol
~108~
LRC CHK
‘7’
‘7’
END
CR
LR
RTU mode
:
Address
01H
Function
86H
Exception code
02H
CRC CHK Low
C3H
CRC CHK High
A1H
b) Meaning of fault code
:
Fault code
Description
01
Function code fault
:
inverter only identify functions of 03H, 06H, 08H
02
Command address error
Address inverter does not exist in the command.
03
Command content is wrong:
Command content is out of range, e.g.: when write parameters,
command parameter value are beyond limits.
04
Command can not be implemented.
Inverter can not perform the command, e.g.: command modifies read-
only data or parameter.
09
Check code error
Check byte of command data frame is not correct.
12
Command data is too short.
(
less than 17 bytes at ASCII mode, RTU less than 8 bytes at RTU
mode.
)
13
Command data is too long,
total bytes is not beyond 27 bytes in ASCII mode
(
that is to say, the
data bit is not beyond 10 bytes
),
total bytes is not beyond 12 bytes in RTU mode
(
that is to say, the data
bit is not beyond 4 bytes.
)
15
Error occurs when execute writing command.
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...