User Manual of SY5000 series AC Drive Parameter instrction
~45~
○
E-025
Multi-step speed
setting 4
0.00 ~ [b-010]
0.01
Hz
0.00
○
E-026
Multi-step speed
setting 5
0.00 ~ [b-010]
0.01
Hz
0.00
○
E-027
Multi-step speed
setting 6
0.00 ~ [b-010]
0.01
Hz
0.00
○
E-028
Multi-step speed
setting 7
0.00 ~ [b-010]
0.01
Hz
0.00
○
E-029
Each speed accel
/ decel time
command
0 ~ 255
1
0
○
E-030
Positive/negative
characteristic
command
0: positive characteristic;
1: negative characteristic
1
0
○
E-031
Analog input
bias
-
50.0 ~ 50.0
0.1
Hz
0.0
○
E-032
Analog input
gain
0.01 ~ 5.00
0.01
1.00
○
E-033
Pulse frequency
input eguivalent
0.10 ~ 5.00
0.01
Hz
0.10
○
E-034
Meter output
command
0: the voltage between FM
and GND is about 10 V when
output highest frequency;
1: the voltage between FM
and GND is about 5 V when
output rated current
;
2: the voltage between FM
and GND is about 5 V when
output rated voltage
.
1
0
○
E-035
Meter output
gain
0.50 ~ 1.20
0.01
1.00
○
E-036
Skip frequency 1
0.00 ~ [E-036]
0.01
Hz
0.00
○
E-037
Skip frequency 2
[E-036] ~ [E-038]
0.01
Hz
0.00
○
E-038
Skip frequency 3
[E-037] ~ [b-010]
0.01
Hz
0.00
○
E-039
Skip width
0.00 ~ 10.00
0.01
Hz
0.00
○
E-040
Motor stall
level command
0: disabled;
1: enabled
1
1
○
E-041
Motor stall
level
50 ~ 200
1
%
150
○
E-042
Power input
start
0: disabled;
1: enabled
1
0
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...