User Manual of SY5000 series AC Drive MODBUS communication protocol
~107~
Monitor
inverter
status
2106H
Output voltage
2107H
Output current
2108H
DC bus voltage
2109H
Inverter current temperature
210AH
Total running time of inverter
Definition
Parameter
address
Description
210BH
bit 0
Short circuit between PI1 and
COM terminal
0
:
No 1
:
Yes
bit 1
Short circuit between PI2 and
COM terminal
0
:
No 1
:
Yes
bit 2
Short circuit between PI3 and
COM terminal
0
:
No 1
:
Yes
bit 3
Short circuit between PI4 and
COM terminal
0
:
No 1
:
Yes
bit 4
Short circuit between SR and
COM terminal
0
:
No 1
:
Yes
bit 5
Short circuit between SF and
COM terminal
0
:
No 1
:
Yes
bit 6
Short circuit between RST and
COM terminal
0
:
No 1
:
Yes
bit 7
Short circuit between EMS
and COM terminal
0
:
No 1
:
Yes
bit 8~15
Reserved
--
--
5. The slave’s response when communication fault
The host computer generates an error when communicating with the
inverter, the inverter will response the corresponding
fault code
,
reply the
host commands of “Function code”. OR. 80H.
a) Example of response data when an error occurs:
ASCII mode
:
STX
‘:’
Address
‘0’
‘1’
Function code
‘8’
‘6’
Exception code
‘0’
‘2’
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...