User Manual of SY5000 series AC Drive Parameter instrction
~78~
E-058 written prohibition selection
This parameter is used to prevent data from being mistakenly modified
:
E-058 = 0
:
All parameters are allowed to be rewritten;
E-058 = 1
:
Other parameters are prohibited to be modified, except b-000;
E-058 = 2
:
All parameters are prohibited to be rewritten.
If you try to modify parameters under read only state, it will display“-.Err”.
*********************************************************
*
Note
:
In the state of E-058 = 0, although all parameters are allowed to be modified,
some parameters are not allowed to be modified in operation. At this moment, it
will immediately display “¬-.Err” when you try to change parameters. Pleasemodify
parameters after stop the motor.
*********************************************************
E-059 parameter initialization
E-059 = 0——Reserved;
E-059 = 1——All parameter values will be restored to factory settings;
E-059 = 2——Clear all fault information which is recorded by the system.
After initialization, the system will automatically reset this parameter as 0.
E-054 output selection of relay Y1 (for SY5000-P series only)
E-055 operation signal frequency (for SY5000-P series only)
E-056 speed arrival detection amplitude (for SY5000-P series only)
Output of relay Y1 can be any one of operation signal, speed arrival signal or
overload alarm signal. Factory setting is operation signal. Value of [E-054]: 0——
operation signal; 1——frequency arrival signal; 2——overload alarm signal.
Operation signal——if [E-054] setting is 0, output of relay Y1 is operation signal
and operation frequency can be set here ([E-055]). Relay Y1 closes when output
frequency is higher than operation signal frequency, otherwise disconnects.
Frequency arrival signal——if [E-054] setting is 1, output of relay Y1 is
frequency arrival signal and frequency arrival detection amplitude can be set here
([E-056]) . Relay Y1 closes when output frequency is in the range (setting frequency
± speed arrival detection amplitude), otherwise disconnects.
Overload alarm signal——if [E-054] setting is 2, output of relay Y1 is overload
alarm signal. Relay Y1 closes when overload failure happens otherwise disconnects.
Zero speed operation signal——if [E-054] setting is 3, output of relay Y1 is AC
Drive zero speed operation signal. Relay closes when output frequency equals to 0
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...