User Manual of SY5000 series AC Drive Parameter instrction
~48~
○
E-055
Operation
signal
frequency
0.01 ~ [b-010]
0.01
Hz
0.10
○
E-056
Speed reach
detection
amplitude
0.0 ~ 50.0
0.1
Hz
0.0
○
E-057
Keypad display
magnification
0.1 ~ 100.0
0.1
1.0
○
E-058
Writing-
prohibited
command
0: all parameters can be
modified;
1: other parameters are
prohibited to modify, except
[b-000];
2: all parameters are prohibited
to modify;
3~100: no operation.
1
0
Х
E-059
Parameter
initialization
(restore
default)
0: no operation;
1: restore all default
parameters;
2: clear all fault records.
1
0
Code table of PID regulation (group P)
Function
code
Description
Setting range
Increment Unit Default
○
P-000
PID regulation
command
0: disabled;
1: enabled
1
0
○
P-001
The reference
channel
command
0: digital voltage setting ([P-002]) ;
1: digital current setting ([P-003]) ;
2: select analog voltage input V2-
GND
;
3: select analog current inputI
2-GND.
1
0
○
P-002
Digital voltage
setting value
0.00 ~ 10.00
0.01
V
0.00
○
P-003
Digital current
setting value
0.0 ~ 20.0
0.1
mA
0.0
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...