User Manual of SY5000 series AC Drive Parameter instrction
~72~
By connecting frequency meter or voltage meter, it can remotely monitor output
frequency or output current of the inverter.
Please connect a meter (resistance is more than 2KΩ) which full scales is 10V,
manximum allowable output current is 10mA.
E-034 = 0
:
When output highest frequency, output voltage between FM-COM is
10V
;
E-034 = 1
:
When output rated current, output voltage between FM-COM is 5V.
Due to effect of load change, output current will contain ±15% bias
;
E-034 = 2
:
When output rated voltage, output voltage between FM-COM is 10V.
By setting E-035, it can adjust output voltage, so don’t need connect the variable
resistor for the use of full-scale calibration. Maximum output voltage is about 10.6V.
E-036 skip frequency 1
E-037 skip frequency 2
E-038 skip frequency 3
E-039 skip frequency width
Skip frequency function is mainly used to prevent mechanical vibration of the
load (noise) and avoid occurrence of resonance.
(
1
)
Jump point can be set up to 3, namely E-036, E-037, E-038
。
(
2
)
When jump width
(
E-039
)
is set as 0.00 Hz, jump is disabled
(
3
)
Three skip frequency ranges can overlap, but make sure E-036
<
E-037
<
E-038
,
the skip frequency overlap region will be consolidated.
(
4
)
This function applies to various situation of frequency settings.
E-040 motor stall level selection
E-041 motor stall level
E-040 = 1, the function of prevention current stall is enabled.
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...