User Manual of SY5000 series AC Drive Parameter instrction
~62~
b-035 motor direction
The function is enabled only when b-001 is 5 (namely panel control enabled),
and the parameter is used to decide motor motional direction. The function is
inenabled when b-001 is 0 (namely panel control inenabled), and the parameter setting
is inenabled (please see setting instruction of b-001).
b-035 = 0
:
commanding motor rotating forward
;
b-035 = 1
:
commanding
motor rotating reversely
Default is 0, namely commanding motor rotating forward.
b-036 SF
,
SR terminal function
If b-001 is 0, namely when panel control inenabled, run/stop and motional
direction is controlled by SF, SR terminals.
(
1
)
FWD-REV mode
(
b-036 = 0
)
SF
,
SR terminal status
Motor status
SF-COM connect
,
SR- COM disconnect
Forward running
SF- COM disconnect
,
SR- COM connect
Reverse running
Both of SF- COM
,
SR- COM disconnect
Stop running
(
inverter standby
)
Both of SF- COM
,
SR- COM are connect
Stop running
(
inverter standby
)
(
2
)
RUN/ FWD-REV mode
(
b-036 = 1
)
SF
、
SR terminal status
Motor status
SF- COM connect
,
SR- COM disconnect
Forward running
SF- COM
,
SR- COM connect
Reverse running
SF- COM
,
SR- COM disconnect
Stop running
(
inverter standby
)
SF- COM disconnect
,
SR- COM connect
Stop running
(
inverter standby
)
(
3
)
FWD-REV/ self-sustaining mode
(
b-036 = 2
)
Forward
Reverse
Содержание SY5000 series
Страница 1: ......
Страница 2: ......
Страница 4: ...User Manual of SY5000 series AC Drive Overview 1 2 Instruction of model no 1 3 Nameplate instruction ...
Страница 11: ...User Manual of SY5000 series AC Drive Installation Figure 2 2 a 11KW 160KW Figure 2 2 b 185KW ...
Страница 21: ...User Manual of SY5000 series AC Drive Wiring 19 Figure 3 2b Connection diagram of SY5000 G series 18 5KW ...
Страница 22: ...User Manual of SY5000 series AC Drive Wiring 20 Figure 3 3a Connection diagram of SY5000 P series 18 5KW ...
Страница 83: ...User Manual of SY5000 series AC Drive Parameter instrction 81 ...