5.
Check that all pins of the AC plug are free of voltage. Use a
suitable voltmeter for this (do not use a simple neon phase
checker).
NOTICE!
Risk of damage to the inverter or derating!
–
The mounting location must satisfy the following
conditions:
–
The mounting location and immediate
environment are permanently fixed, vertical,
flat, non-inflammable and not subject to
constant vibration.
–
The permissible ambient conditions are
conformed to; see Technical data
–
The following free spaces must be present
around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
–
Do not install the inverter in areas where animals
are kept.
–
Observe the connection ratings specified on the
type plate.
–
The DC cables must not be connected to an earth
potential (DC inputs and AC output are not
galvanically isolated).
NOTICE!
When transmitting data over a public network:
–
Transmitting data over a public network may
result in additional costs.
–
Data transmitted over a public network is not
protected from unauthorised access by third-
parties.
Note
–
Avoid exposing the inverter to direct sunlight.
–
The display must be readable on the installed
device.