At the inverter you wish to test, Italy is selected as country setting.
1.
Check the country setting via
Information
▶
System info
in the main menu as required.
2.
Select
Self test
in the main menu.
ð
The dialog shown on the left is displayed.
3.
Press and hold
SET
for 1 second.
ð
The self test starts.
The values for the first test phase are displayed (Fig. left).
4.
Press
s
to display the values for the subsequent test phases
(if available).
5.
Only when
Self test failed
is displayed: Press
SET
to
confirm the message.
✔
The status display appears.
NOTICE!
If
Self test failed
is displayed then repeat the
self test as soon as possible so that the inverter can
resume feeding.
1.
Press
s
several times until the message
Self test passed
is displayed (Fig. left).
2.
Press
SET
to confirm the result of the self test.
✓
The status display appears.
Operation
When the self test has
finished, proceed as
follows:
EN
747,431 | Z09.2 | 18/02/2016
61