NOTICE!
P %
cannot be changed at the first and last nodes
(
000 %
,
100 %
).
1.
Press
rs
to select a parameter for the node.
2.
Press
SET
.
ð
The parameter value flashes.
3.
Press
rs
to change the value.
4.
Press
SET
.
ð
The change is adopted.
5.
Repeat steps 1 to 4 for the other parameters.
6.
Press
ESC
.
✓
The check list is shown.
1.
The previously set reactive power characteristic curve is
displayed graphically (example in Fig. left).
2.
Press
ESC
✓
The check list is shown.
✔
Finish
has been selected in the check list and
SET
has been
pressed. One of 2 possible dialogues is displayed.
1.
Proceed as follows, depending on the respective dialogue:
n
Dialogue
Settings are incomplete
: Press
SET
and
work through the open items in the check list.
n
Dialogue
Are all settings correct?
:
Press
ESC
to correct settings or
2.
Press and hold
SET
(> 1 s) to finish 1st commissioning.
✓
If
SET
was pressed for a longer time then the inverter
starts anew and synchronises itself with the grid (Fig. left).
Node n
Display char. curve
Finish
EN