Notice
With a mains grid voltage of 100 V ... 127 V, the
inverter can be connected between the L1, L2 and L3
external conductors as follows:
2-phase mains grids
–
N and L are connected between the L1 – L2
external conductors at the inverter side. See
②
and
③
–
One of the two connected external conductors is
connected to PE at the inverter side. This
connection can be made within the AC plug or in
an external junction box.
Fig. 12 shows an example of an inverter-side
connection between L1 and PE:
Top: Connection
①
in the AC plug
⑤
Bottom: Connection
④
in an external junction
box
⑥
)
3-phase mains grids
–
N and L are connected between the L1 – L2 or
L1 – L3 or L2 – L3 external conductors at the
inverter side.
–
One of the two connected external conductors is
connected to PE at the inverter side. This
connection can be made within the AC plug or in
an external junction box.
Fig. 12 shows an example of an inverter-side
connection between L1 and PE:
Top: Connection
①
in the AC plug
⑤
Bottom: Connection
④
in an external junction
box
⑥
)
The external conductor voltages are shown in Fig. 13.
1.
Wire the AC plug supplied for the selected external
conductors as described in the Appendix
2.
Connect one of the two connected phases to PE at the
inverter side. Make this connection inside the AC plug or use
an external junction box, as shown in Fig. 12.
3.
Close the AC plug.
EN
747,431 | Z09.2 | 18/02/2016
36
Содержание coolcept StecaGrid 1500
Страница 1: ...Installation and operating instructions EN coolcept coolcept x 747 431 Z09 2 2016 02 18...
Страница 57: ...Fig 20 Email confirming successful registration EN 747 431 Z09 2 18 02 2016 57...
Страница 85: ...Appendix EN 747 431 Z09 2 18 02 2016 85...
Страница 93: ...747 431 Z09 2 2016 02 18...
Страница 94: ......