Chapter 5 Function parameter
44
Ch
ap
ter 5
261. F8.02
Motor overload protection
selection
0: Invalid 1: Enable
1
☆
262. F8.03
Motor overload protection
gain
0.20 to 10.00
1.00
☆
263. F8.04
Motor overload pre-alarm
coefficient
50% to 100%
80%
☆
264. F8.05 Over-voltage stall gain
0 to 100
0
☆
265. F8.06
Over-voltage stall
protection voltage / energy
consumption brake
voltage
120% to 150%
130%
☆
266. F8.07
Input phase loss protection
selection
Units digit: Input phase loss
protection selection
0: Invalid 1: Enable
Tens digit: contactor actuation
protection
0: Invalid 1: Enable
11
☆
267. F8.08
Output phase loss
protection selection
0: Invalid 1: Enable
1
☆
268. F8.09 Short to ground protection 0: Invalid 1: Valid
1
☆
269. F8.10
Number of automatic fault
reset
0 to 32767
0
☆
270. F8.11
Fault DO action selection
during automatic fault
reset
0: OFF
1: ON
0
☆
271. F8.12
Automatic fault reset
interval
0.1s to 100.0s
1.0s
☆
272. F8.13
Over-speed detection
value
0.0 to 50.0% (maximum frequency)
20.0%
☆
273. F8.14 Over-speed detection time 0.0 to 60.0s
1.0s
☆
274. F8.15
Detection value for too
large speed deviation
0.0 to 50.0% (maximum frequency)
20.0%
☆
275. F8.16
Detection time for too
large speed deviation
0.0 to 60.0s
5.0s
☆
276. F8.17
Fault protection action
selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(same as units digit)
Hundred digit: output phase loss
(Err.13) (same as units digit)
Thousand digit: external fault
(Err.15) (same as units digit)
00000
☆