Chapter 2 Standard specifications
11
Ch
ap
ter 2
function
Quick current
limiting
The current limiting algorithm is used to reduce the inverter over
current probability, and improve whole unit anti-interference
capability.
Timing control
Timing control function: time setting range (0m to 6500m)
R
u
n
n
in
g
In
p
u
t
si
g
n
al
Running
method
Keyboard/terminal/communication
Frequency
setting
10 frequency settings available, including adjustable DC (0 to 10V/
-10V to 10V), adjustable DC (0 to 20mA), panel setting, etc.
Start signal
Rotate forward/reverse
Multi-speed
At most 16-speed can be set (run by using the multi-function
terminals or program)
Emergency
stop
Interrupt controller output
Wobbulate run Process control run
Fault reset
When the protection function is active, you can automatically or
manually reset the fault condition.
PID feedback
signal
Including DC (0 to 10V), DC (0 to 20mA)
O
u
tp
u
t
S
ig
n
al
Running status
Motor status display, stop, ac/deceleration, constant speed,
program running status.
Fault output
Contact capacity :normally closed contact 3A/AC 250V, normally
open contact 5A/AC 250V, 1A/DC 30V.
Analog output
Two-way analog output, 16 signals can be selected such as
frequency, current, voltage and other, output signal range (0 to 10V
/ 0 to 20mA).
Output signal
At most 4-way output, there are 40 signals each way
Run function
Limit frequency, jump frequency, frequency compensation, auto-
tuning, PID control
DC current
braking
Built-in PID regulates braking current to ensure sufficient braking
torque under no overcurrent condition.
Running command
channel
Three channels: operation panel, control terminals and serial
communication port. They can be switched through a variety of
ways.
Frequency source
Total 10 frequency sources: digital, analog voltage, analog current,
multi-speed and serial port. They can be switched through a variety
of ways.
Input terminals
8 digital input terminals, compatible with active PNP or NPN input
mode, one of them can be for high-speed pulse input (0 to 100 kHz
square wave); 3 analog input terminals for voltage or current input.
Output terminals
2 digital output terminals, one of them can be for high-speed pulse
output(0 to 100kHz square wave); one relay output terminal; 2
analog output terminals respectively for optional range (0 to 20mA
or 0 to 10V), they can be used to set frequency, output frequency,
speed and other physical parameters.
Pr
o
te
ct
io
n
f
u
n
ct
io
n
Inverter protection
Overvoltage protection, undervoltage protection, overcurrent
protection, overload protection, overheat protection, overcurrent
stall protection, overvoltage stall protection, losting-phase
protection (optional), communication error, PID feedback signal
abnormalities, PG failure and short circuit to ground protection.
IGBT temperature
display
Displays current temperature IGBT