Chapter 5 Function parameter
79
Ch
ap
ter 5
can be viewed at d0.41)
40
Current running time of
arrival
When the inverter starts running time is longer than the time
set by F7.45, it outputs ON signal.
F2.06
High-speed pulse output function selection
0~17
0
☆
F2.07
DA1 output function selection
0~17
2
☆
F2.08
DA2 output function selection
0~17
13
☆
High-speed pulse output frequency range of 0.01kHz ~ F2.09 (high speed pulse output
maximum frequency), F2.09 can be set between 0.01kHz ~ 100.00kHz.
Analog Output DA1 and DA2 output range is 0V ~ 10V, or 0mA ~ 20mA. Pulse output or
analog output range, with the corresponding scaling function relationship in the following table:
Setting
value
Functions
Description
0
Running frequency
0~Max. output frequency
1
Set frequency
0~Max. output frequency
2
Output current
0~2 times the motor rated current
3
Output torque
0~2 times the motor rated toqure
4
Output power
0~2 times rated power
5
Output voltage
0~1.2 times inverter rated voltage
6
High speed pulse input
0.01kHz~100.00kHz
7
Analog AI1
0V~10V (or 0~20mA)
8
Analog AI2
0V~10V (or 0~20mA)
9
Analog AI3
0V~10V
10
Length value
0~Max. setting length
11
The count value
0~Max. count value
12
Communication set
0.0%~100.0%
13
Motor speed
0~Max. output frequency correspondent speed
14
Output current
0.0A~100.0A (Inverter power
≦
55kW);
0.0A~1000.0A (Inverter power>55kW)
15
DC bus voltage
0.0V~1000.0V
16
Reserved
Reserve
17
Frequency source main set
0~Max. output frequency
F2.09 Maximum frequency of high-speed pulse 0.01kHz~100.00kHz
50.00kHz
☆
When the SPB terminal as a pulse output, the function code is used to select the maximum
output pulse frequency value.
F2.10
SPB output delay
0.0s~3600.0s
0.0s
☆
F2.11
Relay 1 output delay time
0.0s~3600.0s
0.0s
☆
F2.12
Expansion card DO output delay time
0.0s~3600.0s
0.0s
☆
F2.13
SPA output delay time
0.0s~3600.0s
0.0s
☆
F2.14
Relay 2 output delay time
0.0s~3600.0s
0.0s
☆
Set the output terminal SPA, SPB, relay 1, relay 2, delay time of changing from the state
produced to the actual output differentiated.
F2.15
DO terminal
active status
selection
Units digit
SPB switching active status selection
00000
☆
Positive
0
Negtive
1
Tens digit
Relay 1 active setting (0 to 1, as
defined in units digit)
Hundreds digit
Reserve
Thousands digit
SPA Terminal active state settings
(0 to 1, as defined in units digit)
Tens thousand
Relay 2 active setting (0 to 1, as