Chapter 5 Function parameter
51
Ch
ap
ter 5
reference manner
1: Analog AI1 reference
2: Analog AI2 reference
3: Panel potentiometer setting
4: High-speed pulse setting
5: PID control setting
6:Keyboard set frequency (F0.01)
setting, UP/DOWN can be
modified
7. Analog AI3 given
5-1-17.
E2 Group - PID function
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge
384. E2.00 PID setting source
0: E2.01 setting
1: Analog AI1 reference
2: Analog AI2 reference
3: Panel potentiometer setting
4: High-speed pulse setting
5: Communications reference
6: Multi-stage command reference
7: AI3
0
☆
385. E2.01 PID keyboard reference
0.0% to 100.0%
50.0%
☆
386. E2.02 PID feedback source
0: Analog AI1 reference
1: Analog AI2 reference
2: Panel potentiometer setting
3: AI1-AI2 reference
4: High-speed pulse setting
5: Communications reference
6: AI1+AI2 reference
7: MAX(|AI1|, |AI2|) reference
8: MIN (|AI1|, |AI2|) reference
9: Analog AI3 reference
0
☆
387. E2.03 PID action direction
0: positive 1: negative
0
☆
388. E2.04 PID setting feedback range
0 to 65535
1000
☆
389. E2.05
PID inversion cutoff
frequency
0.00 to F0.19 (maximum
frequency)
0.00Hz
☆
390. E2.06 PID deviation limit
0.0% to 100.0%
2.0%
☆
391. E2.07 PID differential limiting
0.00% to 100.00%
0.10%
☆
392. E2.08 PID reference change time
0.00s to 650.00s
0.00s
☆
393. E2.09 PID feedback filter time
0.00s to 60.00s
0.00s
☆
394. E2.10 PID output filter time
0.00s to 60.00s
0.00s
☆
395. E2.11
PID feedback loss detection
value
0.0%: feedback loss not judged
0.1% to 100.0%
0.0%
☆