Chapter 5 Function parameter
101
Ch
ap
ter 5
Thousands
digit
Reserved
Ten
thousands
digit
Reserved
When "free stop" is selected, the inverter displays Err. *, and directly stops.When "Stop at the
selected mode" is selected, the inverter displays Arr. *, firstly stops at the selected mode and then
displays Err. * When "continue to run" is selected, the inverter continues to run and displays Arr. *,
the operating frequency is set by F8.24.
F8.21~
F8.23
Reserved
F8.24 Fault running frequency
current frequency running
0
0
☆
setting frequency running
1
upper frequency running
2
down frequency running
3
Abnormal reserve frequency
running
4
F8.25 Abnormal reserve frequency
60.0%~100.0%
100%
☆
When the inverter occurs faults during operation, and the troubleshooting mode for the fault
is set to "continue to run", the inverter displays Arr. *, and runs at the operating frequency set by
F8.24.
When "abnormal spare frequency" is selected, the value set by F8.25 is the percentage of the
maximum frequency.
F8.26 Momentary power cut action selection
Invalid
0
0
☆
Deceleration
1
Deceleration and stop
2
F8.27 Reserved
F8.28
Recovery voltage judgment time of
momentary power cut
0.00s~100.00s
0.50s
☆
F8.29
Judgment voltage of momentary power
cut
50.0%~100.0%(standard bus
voltage)
80.0%
☆
Bus voltage
Time(t)
Deceleration time 3
Time(t)
Running
frequency
Recovery
acceleration time
F8.26=1(Deceleration)
Judgment voltage of
momentary power cut action
F8.27
Recovery voltage judgment time
F8.28
Deceleration time 4
(F8.26=2:
Deceleration
)
Voltage protection of
momentary power out
F8.29
Running
frequency
Time(t)
Figure 5-28:
Schematic diagram of momentary power cut action