Chapter 5 Function parameter
76
Ch
ap
ter 5
Thousands digit
DI9 Terminal active state set
(0~1, same as the units digit)
Ten Thousands
digit
DI10 Terminal active state set
(0~1, same as the units digit)
For setting the digital input terminal of the active mode. When selecting high effective,
appropriate DI terminal and COM communicated effectively, disconnect invalid. Select is low
effective, appropriate DI terminal and COM connectivity invalid, disconnect effective
。
F1.37 DI1 delay time
0.0s~3600.0s
0.0s
★
F1.38 DI2 delay time
0.0s~3600.0s
0.0s
★
F1.39 DI3 delay time
0.0s~3600.0s
0.0s
★
DI terminal for setting status changes, changes in the delay time of the inverter.
Currently only DI1, DI2, DI3 with delay time setting function.
F1.40 Define the input terminal repeat
0: unrepeatable; 1: repeatable
0
★
0: unrepeatable Two different multi-function input terminals can not be set to the same
function.
1: repeatable You can repeat two different multi-function input terminal can be set to the same
function.
F1.41 Keyboard encoder X1
0~100.00%
0.00%
☆
Keyboard encoder set value start point
F1.42 Keyboard encoder X2
0~100.00%
100.00%
☆
Keyboard encoder set value end point
F1.43 Keyboard encoder setting value
0~100.00%
-
☆
Display keyboard encoder value, through the keyboard encoder can modify Settings under
monitoring menu.
Keyboard encoder Settings can be used as frequency analogy, setting frequency = maximum
frequency x keyboard encoder Settings.
Eg.: Keyboard encoder Settings can be used as a PID given value, PID given value=
Keyboard encoder Settings.
F1.44
Keyboard encoder X1 correspondent
value is Y1
-100.00%~+100.00%
0.00%
☆
F1.45
Keyboard encoder X2 correspondent
value is Y2
-100.00%~+100.00%
100.00%
☆
The end of the
corresponding value
The start of the
corresponding value
end
start
The end of the
corresponding value
The start of the
corresponding value
end
start
Figure 5-8:Keyboard encoder X correspondent value is Y
F1.46
Keyboard
encoder
control
Units digit
Keyboard encoder power-down to save state
00
☆
Power-down save
0
Power down zero clear
1
Tensdigit
Keyboard encoder setting stop keep
Stop keep
0
With stop command, zero clear
1
Cleared at the end of down time
2
Hundreds digit
Reserve
Thousands digit
Reserve