Chapter 5 Function parameter
39
Ch
ap
ter 5
170.
F5.02 switching frequency 1
0.00 to F5.05
5.00Hz
☆
171.
F5.03 Speed loop ratio G2
0 to 100
20
☆
172.
F5.04 Speed loop integral T2
0.01s to 10.00s
1.00s
☆
173.
F5.05 switching frequency 2
F5.02 to F0.19(max.
frequency)
10.00
Hz
☆
174.
F5.06 Speed loop integral
0: invalid 1: valid
0
☆
175.
F5.07 Torque limit upper limit source
0 to 8
0
☆
176.
F5.08
Upper limit digital setting for
torque
0.0% to 200.0%
150.0%
☆
177.
F5.09 Vector control differential gain
50% to 200%
150%
☆
178.
F5.10 Speed loop filter time constant
0.000s to 0.100s
0.000s
☆
179.
F5.11 Vector control overexcitation gain
0 to 200
64
☆
180.
F5.12
Excitation regulator proportional
gain
0 to 60000
2000
☆
181.
F5.13 Excitation regulator integral gain
0 to 60000
1300
☆
182.
F5.14 Torque regulator proportional gain
0 to 60000
2000
☆
183.
F5.15 Torque regulator integral gain
0 to 60000
1300
☆
5-1-8.
F6 Group - Keyboard and display
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge
184.
F6.00 STOP/RESET key functions
0: STOP/RES key is enabled only
under keyboard operation mode
1:STOP/RES key is enabled under
any operation mode
1
☆
185.
F6.01
Running status display
parameters 1
0x0000 to 0xFFFF
001F
☆
186.
F6.02
Running status display
parameters 2
0x0000 to 0xFFFF
0000
☆
187.
F6.03
Stop status display
parameters
0x0000 to 0xFFFF
0033
☆
188.
F6.04 Load speed display coefficient 0.0001 to 6.5000
3.0000
☆
189.
F6.05
Decimal places for load
speed display
0:0 decimal places
2:2 decimal places
1:1 decimal places
3:3 decimal places
1
☆
190.
F6.06
Inverter module radiator
temperature
0.0
℃
to 100.0
℃
-
●