Chapter 5 Function parameter
46
Ch
ap
ter 5
284. F8.27 Reserved
285. F8.28
Recovery voltage
judgment time of
momentary power cut
0.00s to 100.00s
0
☆
286. F8.29
Judgment voltage of
momentary power cut
action
50.0% to 100.0% (standard bus
voltage)
10%
☆
287.
F8.30~
F8.32
Reserved
288. F8.33
motor temperature sensor
type
0: Invalid; 1: PT100 detect
0
☆
289. F8.34
motor over heat protection
value
0~200
110
☆
290. F8.35
motor over heat alma
value
0~200
90
☆
5-1-11.
F9 Group - Communication parameter
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge
291. F9.00 Baud rate
Units digit:MODBUS
Tens digit:Profibus-DP
Hundreds digit:Reserve
Thousands digit:CAN bus baudrate
6005
☆
292. F9.01 Data format
0: no parity (8-N-2) 2: odd parity (8-O-1)
1: even parity (8-E-1); 3: no parity (8-N-1)
0
☆
293. F9.02 This unit address
1-250, 0 for broadcast address
1
☆
294. F9.03 Response delay
0ms-20ms
2ms
☆
295. F9.04
Communication
timeout time
0.0 (Invalid); 0.1~60.0s
0.0
☆
296. F9.05 Data protocol selection
Units digit: MODBUS
0: non-standard MODBUS protocol
1: standard MODBUS protocol
Tens digit: Profibus-DP
0: PP01 format
1: PP02 format
2: PP03 format
3: PP05 format
31
☆
297. F9.06 Current resolution
0: 0.01A 1: 0.1A
0
☆
298. F9.07
Communication
card type
0:Modbus communication card
1:Profibus communication card
2:Reserved
3:CAN bus communication card
0
☆