Appendix V
170
A
p
p
en
d
ix
V
V-8-3 Parameter setting:
No.
Code
Parameter name
Setting range
F0.11 Command source selection
Terminal block control (LED on)
1
F0.03 Frequency source master setting
UP/DOWN can be modified,
power-down with memory
1
F1.10 Terminal command mode
Three-wire control mode 1
2
F1.00 DI1 terminal function selection
Forward run (FWD)
1
F1.01 DI2 terminal function selection
Three-wire operation control
3
F1.02 DI3 terminal function selection
Reverse run(REV)
2
F1.03 DI4 terminal function selection
terminal UP
6
F1.04 DI5 terminal function selection
terminal DOWN
7
F1.11 Terminal UP/DOWN change rate
Used to set terminal UP/DOWN
adjustment frequency, the rate of
frequency change.
1.00Hz/s
F0.10 UP/DOWN reference
Running frequency
0
V-9. External analog speed control (external 0 ~ 10V voltage
signal given)
V-9-1 electrical diagram:
Circuit breaker
380/400V 50/60Hz
Three phase input power supply
Motor
%
M
0 ~ +10V DC
(Defa ult)
FWD/STOP
REV/STOP
External simulation speed regulation
(External 0 ~ 10V voltage signal given)
0~10V Analog signal
ST500
V-9-2 Connection:
The (+) terminal of the external analog signal is connected to the AI1 terminal,
and the other terminal of the signal is connected to the GND terminal of the inverter.